EA370 — HV Connection — System

Ausgrid · Available · High voltage · 2026–27

Sydney, the Central Coast and the Hunter region.

EA370 HV Connection — System tariff guide

Who it’s for

System-connected sites supplied at high voltage.

What you pay

You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.

If you get solar

Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.

If you get a battery

A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.

Check before you decide

  • Confirm this code on a current retailer bill.
  • Use 12 months of interval data. Check the time of each billed peak.
  • Get kW, kVA and power-factor data from the billing meter.
  • Get an engineering review before you select equipment.
2026–27 network prices

What it costs, and when

These are the network’s charges only. Your retailer adds its own prices on top.

EA370 in one day

Peak is 3pm–9pm on working weekdays, November–March and June–August only.

What the network charges

Access
7979.2649 c/day
Peak energy
4.0147 c/kWh
Off-peak energy
1.9792 c/kWh
Peak capacity
34.6232 c/kVA/day

When the rates apply

3pm–9pm on working weekdays in November–March and June–August. All other times.

Illustrative example

Lower EA370 system capacity by 100 kVA

  • This is a high-voltage system connection.
  • The new rolling maximum is 100 kVA lower.
  • The lower value applies for 365 charge days.
100 kVA × 34.6232 c/kVA/day × 365 days ÷ 100Illustrative network-charge reduction: $12,637.47 a year, excluding GST.

This tariff uses the highest qualifying half-hour in the previous 12 months. One lower peak does not remove an earlier maximum. Confirm the retailer pass-through and power factor.

Would a battery help?

A guide, not a quote

Strong fit

Peak-kVA control

A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.

A battery can reduce these

  • The active-power contribution to the measured kVA maximum.
  • Peak-period grid energy when the battery discharges at the same time.
  • Solar spill that can be stored without sacrificing the required peak reserve.

A battery can’t change these

  • Daily access, metering and other fixed charges.
  • Reactive-power demand unless the inverter and control design explicitly provide power-factor support.
  • A new maximum created after the battery empties or misses dispatch.

You’d need to check

  1. At least 12 months of interval data, including every billed maximum.
  2. Demand timestamps, seasonal windows and billing reset rules.
  3. kW, kVA, kvar and power-factor data at the billing meter.
  4. Retailer rates plus the network tariff—not a blended cents-per-kWh assumption.