Who it is for
Sites supplied at high or sub-transmission voltage.
Essential Energy · BHND3AO, BSSD3AO · 2026–27
Sites supplied at high or sub-transmission voltage.
Regional, rural and remote NSW, including most areas outside the major coastal networks.
The exact 2026–27 network rates sit side by side. Open a code below for the worked example, the charge window and the checks before you change anything.
| Code | What it is | Status | Access | Energy | Demand / capacity | Export | Battery fit |
|---|---|---|---|---|---|---|---|
| BHND3AOHV Business DemandHigh voltage | Daily access, peak/shoulder/off-peak energy and time-banded kVA demand charges. | Default |
|
|
| — | Strong |
| BSSD3AOSub-transmission DemandSub-transmission | Daily access, peak/shoulder/off-peak energy and time-banded kVA demand charges. | Default |
|
|
| — | Strong |
These codes share a charging method. The differences are in the rates, the time bands and who each code is for.
Sites supplied at high or sub-transmission voltage.
Same maths as the large-business family, at higher voltages. Get an engineering review before choosing equipment.
Open a code for its exact rates, the charge window, a worked example and the checks worth running before you change anything.
Businesses connected and metered at high voltage.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Weekdays only — weekends are all off-peak.
On weekdays, off-peak is 12am–7am, shoulder is 7am–10am, peak is 10am–3pm, shoulder is 3pm–5pm, peak is 5pm–8pm, shoulder is 8pm–10pm, and off-peak is 10pm–12am. Weekends are off-peak. Interval meters use daylight saving time. Each band has its own monthly half-hour kVA maximum.
The tariff is only one part of an HV project. Engineering and connection costs can control the result.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Connections supplied at Essential Energy sub-transmission voltage.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Weekdays only — weekends are all off-peak.
On weekdays, off-peak is 12am–7am, shoulder is 7am–10am, peak is 10am–3pm, shoulder is 3pm–5pm, peak is 5pm–8pm, shoulder is 8pm–10pm, and off-peak is 10pm–12am. Weekends are off-peak. Interval meters use daylight saving time. The tariff uses a separate monthly half-hour kVA maximum in each band.
Sites above 10 MW or 40 GWh a year may have site-specific arrangements. Confirm the actual contract.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Short answers to the things people ask before they change a tariff.
BHND3AO is the Essential Energy HV Business Demand tariff. It is a default high voltage tariff for Business sites supplied and metered at high voltage. Daily access, peak/shoulder/off-peak energy and time-banded kVA demand charges.
BSSD3AO is the Essential Energy Sub-transmission Demand tariff. It is a default sub-transmission tariff for Connections supplied at Essential Energy sub-transmission voltage. Daily access, peak/shoulder/off-peak energy and time-banded kVA demand charges.
Same maths as the large-business family, at higher voltages. Get an engineering review before choosing equipment. For BHND3AO, the battery signal is strong: A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
The charges are Daily access, Time-of-use energy, kVA demand charge. On weekdays, off-peak is 12am–7am, shoulder is 7am–10am, peak is 10am–3pm, shoulder is 3pm–5pm, peak is 5pm–8pm, shoulder is 8pm–10pm, and off-peak is 10pm–12am. Weekends are off-peak. Interval meters use daylight saving time. Each band has its own monthly half-hour kVA maximum.
Sites supplied at high or sub-transmission voltage. The code on your retailer bill is the starting point. Your retailer must confirm any tariff assignment or change.
Effective 1 July 2026. Published network prices exclude GST. These are the network charges only. Your retailer adds its own prices and may package the structure differently.
Reviewed by Mike Anderson · Last verified 7 November 2026
Effective 1 July 2026. Published network prices exclude GST. These are network charges only; your retailer adds its own prices.