Who it is for
Large and very large low-voltage sites. EA314/EA315 are the embedded-network parent versions.
Ausgrid · EA305, EA314, EA310, EA315 · 2026–27
Large and very large low-voltage sites. EA314/EA315 are the embedded-network parent versions.
Sydney, the Central Coast and the Hunter region.
The exact 2026–27 network rates sit side by side. Open a code below for the worked example, the charge window and the checks before you change anything.
| Code | What it is | Status | Access | Energy | Demand / capacity | Export | Battery fit |
|---|---|---|---|---|---|---|---|
| EA305LV 160–750 MWh — SystemLow voltage | Daily access, peak/off-peak energy and a kVA capacity charge. | Available |
|
|
| — | Strong |
| EA314LV 160–750 MWh — Embedded NetworkLow voltage | Daily access, peak/off-peak energy and embedded-network kVA capacity pricing. | Available |
|
|
| — | Strong |
| EA310LV Above 750 MWh — SystemLow voltage | Higher daily access, peak/off-peak energy and a kVA capacity charge. | Available |
|
|
| — | Strong |
| EA315LV Above 750 MWh — Embedded NetworkLow voltage | Higher daily access, peak/off-peak energy and embedded-network kVA capacity pricing. | Available |
|
|
| — | Strong |
These codes share a charging method. The differences are in the rates, the time bands and who each code is for.
Large and very large low-voltage sites. EA314/EA315 are the embedded-network parent versions.
Solar trims energy. A battery helps the kVA charge only partly — kVA includes reactive power, so fix power factor first.
Open a code for its exact rates, the charge window, a worked example and the checks worth running before you change anything.
Businesses connected directly to the low-voltage network using 160–750 MWh a year.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Peak is 3pm–9pm on working weekdays, November–March and June–August only.
3pm–9pm on working weekdays in November–March and June–August. All other times.
50 kVA × 57.7962 c/kVA/day × 365 days ÷ 100Illustrative network-charge reduction: $10,547.81 a year, excluding GST.This tariff uses the highest qualifying half-hour in the previous 12 months. One lower peak does not remove an earlier maximum. A 50 kW battery does not guarantee a 50 kVA reduction.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Main connections for embedded networks at low voltage using 160–750 MWh a year.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Peak is 3pm–9pm on working weekdays, November–March and June–August only.
3pm–9pm on working weekdays in November–March and June–August. All other times.
50 kVA × 68.7649 c/kVA/day × 365 days ÷ 100Illustrative network-charge reduction: $12,549.59 a year, excluding GST.This tariff uses the highest qualifying half-hour in the previous 12 months. One lower peak does not remove an earlier maximum. Confirm the parent-meter load and power factor.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Businesses connected directly to the low-voltage network using more than 750 MWh a year.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Peak is 3pm–9pm on working weekdays, November–March and June–August only.
3pm–9pm on working weekdays in November–March and June–August. All other times.
50 kVA × 59.5298 c/kVA/day × 365 days ÷ 100Illustrative network-charge reduction: $10,864.19 a year, excluding GST.This tariff uses the highest qualifying half-hour in the previous 12 months. One lower peak does not remove an earlier maximum. Model the higher access charge and energy charges separately.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Main connections for embedded networks at low voltage using more than 750 MWh a year.
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
These are the network’s charges only. Your retailer adds its own prices on top.
Peak is 3pm–9pm on working weekdays, November–March and June–August only.
3pm–9pm on working weekdays in November–March and June–August. All other times.
50 kVA × 70.8275 c/kVA/day × 365 days ÷ 100Illustrative network-charge reduction: $12,926.02 a year, excluding GST.This tariff uses the highest qualifying half-hour in the previous 12 months. One lower peak does not remove an earlier maximum. Use the parent-meter load, not one tenant load.
A guide, not a quote
Strong fit
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
Short answers to the things people ask before they change a tariff.
EA305 is the Ausgrid LV 160–750 MWh — System tariff. It is a available low voltage tariff for System-connected low-voltage sites using 160–750 MWh a year. Daily access, peak/off-peak energy and a kVA capacity charge.
EA314 is the Ausgrid LV 160–750 MWh — Embedded Network tariff. It is a available low voltage tariff for Embedded-network parent connections at low voltage using 160–750 MWh a year. Daily access, peak/off-peak energy and embedded-network kVA capacity pricing.
EA310 is the Ausgrid LV Above 750 MWh — System tariff. It is a available low voltage tariff for System-connected low-voltage sites using more than 750 MWh a year. Higher daily access, peak/off-peak energy and a kVA capacity charge.
EA315 is the Ausgrid LV Above 750 MWh — Embedded Network tariff. It is a available low voltage tariff for Embedded-network parent connections at low voltage using more than 750 MWh a year. Higher daily access, peak/off-peak energy and embedded-network kVA capacity pricing.
Solar trims energy. A battery helps the kVA charge only partly — kVA includes reactive power, so fix power factor first. For EA305, the battery signal is strong: A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
The charges are Daily access, Time-of-use energy, kVA capacity charge. 3pm–9pm on working weekdays in November–March and June–August. All other times.
Large and very large low-voltage sites. EA314/EA315 are the embedded-network parent versions. The code on your retailer bill is the starting point. Your retailer must confirm any tariff assignment or change.
Effective 1 July 2026 to 30 June 2027. Published network prices exclude GST. These are the network charges only. Your retailer adds its own prices and may package the structure differently.
Reviewed by Mike Anderson · Last verified 7 November 2026
Effective 1 July 2026 to 30 June 2027. Published network prices exclude GST. These are network charges only; your retailer adds its own prices.
Free instant check
We develop NSW commercial solar projects and introduce you to one installer we would use for that site. It starts here: type an address and we map the actual building live — about ten seconds, no email, no bill upload.