Essential Energy · Optional · Low voltage · 2026–27
Regional, rural and remote NSW, including most areas outside the major coastal networks.
BLND1AB LV Small Business TOU Demand — Opt in tariff guide
Who this is for
Small businesses connected at low voltage using no more than 160 MWh a year with a smart meter.
How the bill works
You pay fixed and energy charges. The bill also uses the highest kVA reading in set periods.
What solar changes
Solar can reduce daytime grid use. If the highest kVA reading occurs after solar output falls, solar alone will not remove it. Solar does not correct poor power factor.
What a battery changes
A battery can reduce the active-power part of the kVA peak. Check power factor before you size it.
Check before you model
Confirm this code on a current retailer bill.
Use 12 months of interval data. Check the time of each billed peak.
Get kW, kVA and power-factor data from the billing meter.
2026–27 network schedule
The price signal behind this code
Network rates only. These are not retail electricity prices.
Published network rates
Access
$2.3784/day
Peak energy
14.6324 c/kWh
Shoulder energy
10.3497 c/kWh
Off-peak energy
6.1014 c/kWh
Peak demand
$9.7035/kVA/month
When it applies
On weekdays, off-peak is 12am–7am, shoulder is 7am–10am, peak is 10am–3pm, shoulder is 3pm–5pm, peak is 5pm–8pm, shoulder is 8pm–10pm, and off-peak is 10pm–12am. Weekends are off-peak. Interval meters use daylight saving time.
Illustrative example
Reduce the billed peak by 50 kVA
The battery reduces the monthly peak maximum from 300 kVA to 250 kVA.
No later interval sets a new maximum.
The example uses the published network demand rate only.
The network demand charge falls by about $485.18 for that month: 50 × $9.7035.
A 100 kW / 200 kWh battery may not reduce a two-hour 300 kW event by 100 kW after losses and site load changes. Check half-hour kVA data.
Battery opportunity lens
Tariff screen—not a savings quote
Strong fit
Peak-kVA control
A controlled battery may reduce the site maximum, but the bill is based on apparent power. Power factor and reactive load can be as important as battery kW.
What dispatch can affect
The active-power contribution to the measured kVA maximum.
Peak-period grid energy when the battery discharges at the same time.
Solar spill that can be stored without sacrificing the required peak reserve.
What it cannot erase
Daily access, metering and other fixed charges.
Reactive-power demand unless the inverter and control design explicitly provide power-factor support.
A new maximum created after the battery empties or misses dispatch.
Evidence required
At least 12 months of interval data, including every billed maximum.
Demand timestamps, seasonal windows and billing reset rules.
kW, kVA, kvar and power-factor data at the billing meter.
Retailer rates plus the network tariff—not a blended cents-per-kWh assumption.